TSI's VelociCalc 9565-P ventilation meter can be used for HVAC testing and balancing, clean room testing, biological safety cabinet and lab fume hood testing, HVAC commissioning and troubleshooting, IAQ investigations, temperature comfort studies, and process air flow testing.
To complete your rental, choose any combination of the following compatible probes: the TSI 995 rotating vane probe, TSI 985 volatile organic compounds probe, TSI 964 air velocity probe, and TSI 982 IAQ probe.
TSI's VelociCalc 9565-P ventilation meter can be used for HVAC testing and balancing, clean room testing, biological safety cabinet and lab fume hood testing, HVAC commissioning and troubleshooting, IAQ investigations, temperature comfort studies, and process air flow testing.
To complete your rental, choose any combination of the following compatible probes: TSI 964 and 966 air velocity probes, and TSI 982 IAQ probe. Need a Pitot probe? We also have this available for rental!
Nextteq Smoke Tube x5 Kit - Optional Add-On Item, Only Sent Upon Request
Rental Includes: TSI VelociCalc 9565 meter w/ selected probe, static pressure probe, two 4 ft neoprene tubing lengths, probe stand, four spare AA batteries, mini USB cable, AC power adapter, TrakPro software and manuals on flash drive (CD may be included), calibration certificates for meter and probes (emailed), and carrying case
Range: 0 to 9,999 ft/min (0 to 50 m/s)
Accuracy: ±3% of reading or ±3 ft/min (±0.015 m/s), whichever is greater
Resolution: 1 ft/min (0.01 m/s)
Probes 964 & 966: 14 to 140°F (–10 to 60°C)
Probe 982: 14 to 140°F (–10 to 60°C)
Accuracy: ±0.5°F (±0.3°C)
Resolution: 0.1°F (0.1°C)
Range: 5% to 95% RH
Accuracy: ±3% RH
Resolution: 0.1% RH
Range: 0 to 5,000 ppm
Accuracy: ±3% of reading or ±50 ppm, whichever is greater
Resolution: 1 ppm
Range: 0 to 500 ppm
Accuracy: ±3% of reading or ±3 ppm, whichever is greater
Resolution: 0.1 ppm
Static / Differential Pressure:
Range: –15 to +15 in. H₂O (±3,735 Pa)
Accuracy: ±1% of reading ±0.005 in. H₂O (±1 Pa)
Resolution: 0.001 in. H₂O (0.1 Pa)
Data Logging: 26,500+ samples and 100 test IDs
Logging Interval: 1 sec to 1 hour
Display: Shows up to 5 measurements at once
Bluetooth & USB: Data transfer via LogDat2™ or TrakPro™
Power: 4 AA batteries or AC adapter
Operating Temp (meter): 40 to 113°F (5 to 45°C)
Storage Temp: –4 to 140°F (–20 to 60°C)
| SKU | 9565-P |
|---|---|
| Manufacturer | TSI Alnor |
| Kit Contents | Datalogging meter with dP sensor and static pressure tip, 8-foot rubber tube, four AA Alkaline batteries, USB cable, power supply, TrakPro and LogDat software CDs, carrying case, user manual, and certificate of calibration. Probes rented separately. |
| Measuring Range Air Velocity | 0 - 15500 Ft/Minute |
| Measuring Range Temperature | 0° - 200°F |
| Shipping Dimensions (LxWxD) | 22x16x14 |
| Weight (lbs) | 36.000000 |
| Power | Batteries, AC Line Power |